WW0792099, Watts, 3/4 IN Lead Free Field Testable, Hose Connection Backflow Preventer, Chome Finish, In-Line

Item #: WW0792099
Manufacturer: Watts
Supplier #: 0792099
Alternate Part #:WW00792099
This 3/4 inch lead free dual check vacuum breaker backflow preventer with atmospheric vent prevent high-hazard backsiphonage backflow and low-head backpressure (10 FT or less) from contaminating the potable water supply. It prevents backflow associated with hose connections when screwed directly to a sill cock, yard hydrant, or wall hydrant. It consists of a lead free brass body with two independently operating rubber and stainless steel check valves, with an atmospheric vent located between the them. It is in-line field testable, non-removable and designed for non-continuous pressure applications. It is ideal for installation in service sinks, chemical dispensers, sill cocks, and frost proof hydrants. Maximum working pressure is 125 psi (10.6 bar).
Call 513-251-4343 for Availability
UOM : EA
Qty:

Item Specifications

  • 3/4
  • Dual Check Vacuum Breaker
  • NPT
  • Lead Free
  • Watts
  • LFN9-CD